A saving is a counterfactual. Measurement and verification exists to make that counterfactual defensible — and the parts that decide whether it holds up are boring: boundary, baseline and uncertainty.
Published 17 November 2026 · about 6 minutes · sources listed at the end · Heattech is a system integrator: the equipment belongs to the manufacturers cited, the integration and the measurement are ours.
Before any meter is installed, write down what is inside the measurement boundary and what is not. Fuel in, useful heat out, and recovered heat — all three have to be inside, or the saving is arithmetic on the wrong numbers.
Auxiliary load is the classic omission: a recovery loop adds a pump, and a pump that runs continuously can eat a visible share of the recovered heat. The Heattech Pulse boundary covers the thermal side — fuel, steam, flue gas and condensate; electrical auxiliary load is outside the measured scope.
The baseline is a period of normal operation you can defend: long enough to cover seasonal load, short enough that the plant has not changed under you. Record load and weather alongside fuel, because a mild month will otherwise look like a successful project.
After every change to the plant — tuning, a new burner curve, an extra recovery stage — the baseline has to be re-established. Mixing pre-change and post-change periods into one claim is the fastest way to lose an argument with a finance team, and the fastest way to lose a dispute with a client.
Two periods rarely have the same load. Normalising means expressing the saving per unit of production or per degree-day rather than per month, so a good saving in a bad month is still visible. In practice: regress fuel against load and ambient over the baseline, then apply the model to the reporting period and compare with what the meters actually show. The difference is the saving, with an error band attached.
Every instrument has a tolerance, and the saving inherits all of them. Meter classes, temperature sensor pairs, the gas meter's own accuracy — state them and combine them into one figure. A claim of "8.5 % ± 0.6 %" survives scrutiny; "8.5 %" invites a challenge you cannot answer.
The professional framework for this is the Efficiency Valuation Organization's IPMVP family of methods (EVO), which separates options for retrofit isolation, whole-facility metering and calibrated simulation. For a heat-recovery retrofit the retrofit-isolation option is usually the right shape: measure the recovered heat directly and keep the rest of the plant as context, not as the claim.
Our demo plant publishes the protocol, the meter list and the live numbers, and the numbers are re-derivable from the raw readings rather than from a summary table. The protocol document is at M&V protocol, and the live figures are on the savings page. If a number cannot be re-derived by a third party, we do not publish it as a saving.
Manufacturer and standards documentation behind the numbers in this article. We are a system integrator: the equipment belongs to the manufacturers named here, the integration and the measurement are ours.