SCREENING TOOL

Size the recovery, then check whether the sink can take it

Type the numbers from the boiler room. The tool balances the flue gas against the water side the way a real audit does — and tells you which of the two is the limit. Same arithmetic that reproduced Cain's own published studies within 4 %.

Inputs

Excess air is derived from O₂: EA = O₂ / (20.9 − O₂). Everything is computed in the browser; nothing you type leaves the page.

Result

Heat available, gas side—
Heat the sink can take—
Recovered (limited side)—
Share of burner input—
Fuel saved—
Value per year—
Simple payback—
CO₂ avoided—
Flue gas dew point—
—

Screening calculation, not a quotation. Final sizing needs a stack traverse, a fuel analysis and the boiler's load profile — that is the site survey, and it is what the paid audit adds.

Ask for the measured audit →

Take the audit report with you

The report carries every input, every intermediate number and the condensing verdict, so a colleague can check it. Enter a work email and we open the finished report — nothing is charged, and no account is needed.

How the two balances work

Gas sideFlue mass = (burner input ÷ fuel heating value) × stoichiometric air/fuel × (1 + EA); then q = ṁ × cp × (Tin − Tout), with cp = 0.27 BTU/lb·°F.
Water sideq = 500 × GPM × ΔT. This is the hard limit: if the sink cannot absorb the heat, the economizer cannot recover it, whatever the flue gas offers.
RecoveredThe smaller of the two. The tool prints which side is limiting on purpose — that single line decides whether you need a bigger coil or a colder sink.
MoneyRecovered heat ÷ boiler efficiency = fuel not bought, because every BTU recovered in the feedwater displaces 1/η BTU at the burner. We print η next to it; a heat-credit calculation without η overstates the saving by 25 % at η = 0.80.
Dew pointComputed from the water vapour in the flue gas. Below it the condensing stage works and latent heat is available; above it you are only moving heat above the water dew point.

Verified against Cain's own published savings studies: water side within 4 %, gas side within 3 % on identical inputs.