Heattech CT · COMBUSTION TRIM

Burn it properly before you recover it

Recovery cannot repair a burner running at the wrong air-fuel ratio. Heattech CT sets the combustion right — excess-air target, damper and fuel curves — so the flue entering the economizer is already as small as the burner allows.

CT means combustion trim. "Trim" is the industry word for the small continuous correction a controller applies on top of the commissioned air-fuel curve: the curve is fixed at commissioning, the trim moves it a few percent either way as oxygen, stack temperature and load drift. Trim is not a tune-up; a tune-up happens once, trim happens every second. Autoflame and Fireye both use the term this way, and so do we.

13.5 %excess air held on the demo plant, band 12–15 %
2.5 %O₂ in the flue at that excess air (2.2–2.7 %)
3load bands tuned: low, mid, high
100 ppmCO ceiling used to prove the tune is safe, not just lean

What is adjusted

Tuning happens on the burner's own control system — typically an Autoflame Mk8 MM with EGA O₂ trim, or the equivalent package on the boiler. We change set points and curves; we never change the flame safeguard logic.

SettingTypical targetWhat it changes
Excess air12 – 15 % (LPG)The dry flue loss — the single biggest burner-side waste
O₂ in flue2.2 – 2.7 %The measurement that proves the excess-air target is held
Fuel / air curvesMatched at 3 load bandsRemoves the lean-at-low-load, rich-at-high-load drift
Flue temperatureAs designed per bandTells you whether recovery still pays at that load
CO< 100 ppm after the tuneConfirms complete combustion — safety, not just efficiency
Servo calibrationVerified at each bandStops the curve from drifting between visits

Excess air by fuel — industry targets

Excess air is the working number: it is what the damper and the O₂ trim actually control, and it is quoted as a percentage of the stoichiometric air. The O₂ column is the same setting read on a flue analyser.

FuelExcess air, commissioning targetO₂ in flueWhy this band
Natural gas5 – 10 %1.0 – 1.9 %Clean, predictable flame — the tightest band is safe
LPG / propane10 – 15 %1.9 – 2.7 %Higher carbon content, denser vapour — needs a little more air
Light fuel oil15 – 20 %2.7 – 3.5 %Atomisation varies with nozzle wear and oil temperature
Heavy fuel oil20 – 25 %3.5 – 4.2 %Viscosity and sulphur — smoke limits set the floor

Ranges are standard commissioning targets for packaged industrial boilers; the final setting is bounded by the burner manufacturer's limits and proven by the CO reading after each adjustment. Below 5 % excess air the CO rises fast — a lean flue is not the same as an efficient one.

How a tune is run

Trim, as the control makers define it

Trim is a vendor discipline before it is ours. The two names a boiler house will recognise:

Fireye NexusThe NX6100 series puts the flame safeguard and the parallel-positioning combustion controller in one package; the NXF4000 model integrates burner management with electronic parallel positioning and O₂ trim in a single controller. Parallel positioning means each actuator (fuel valve, air damper, FGR) has its own positioner, so the air-fuel relationship is set by position, not by a single mechanical linkage.
AutoflameTrim is sold as a control package with an exhaust gas analyser: the EGA reads O₂ (and CO) continuously and the controller corrects the commissioned curve while the boiler runs. Their published large-boiler work is quoted in exactly the terms we use on this site — an O₂ target held across the load range, with the fuel saving stated as a percentage of the bill.

What that means commercially: trim is a vendor product chosen to match the burner, not something we manufacture. Our contribution is either side of it — metering that proves whether the trim actually held after commissioning, and heat recovery that takes the flue the trim has already tightened. A trim claim with no metering behind it is a sales claim; a trim claim with Heattech Pulse behind it is an invoice.

Sources: Fireye parallel positioning controls · Autoflame Mini Mk9.

What it is not

Manufacturer literature

Current issues of the documents this module is built on. Files we are licensed to pass on are served here; the rest we send on request under the manufacturer's own terms.